What We Offer

HFC Clean Agent Fire Suppression Gases

Technical-grade halocarbon fire suppression agents for qualified system manufacturers, distributors, service companies and fire protection professionals.

Request Product & Supply Information

Portfolio

Fire Protection Agent Portfolio

Explore physical properties, common system applications and engineering considerations for four established hydrofluorocarbon (HFC) clean agents. Product-specific quality documentation, availability, packaging and logistics can be discussed with our team.

CF₃CHFCF₃

HFC-227ea

Heptafluoropropane · CAS 431-89-0. Widely used in engineered total-flooding clean-agent systems protecting critical assets.

View technical details →
CF₃CH₂CF₃

HFC-236fa

1,1,1,3,3,3-Hexafluoropropane · CAS 690-39-1. Used in certain portable extinguishers and engineered applications.

View technical details →
CHF₂CF₃

HFC-125

Pentafluoroethane · CAS 354-33-6. Clean-agent option for approved total-flooding system designs.

View technical details →
CHF₃

HFC-23

Trifluoromethane · CAS 75-46-7. Very low boiling point agent used in specialized engineered systems.

View technical details →

Technical Data

Technical Data & Applications

Representative published pure-substance properties. Values are not lot-specific certificates of analysis or a substitute for approved system design manuals.

01 / Clean Agent

HFC-227ea — Heptafluoropropane

Also known in fire protection by the generic designation HFC-227ea; used as the chemical agent in systems marketed under various trade names.

CF₃–CHF–CF₃

Technical Specifications

CAS number431-89-0
Molecular formulaC₃HF₇
Molecular weight170.03 g/mol
Normal boiling point−16.4 °C
Critical temperature101.7 °C
Critical pressureApprox. 29.1 bar
Ozone depletion potential0
Physical formColorless liquefied gas under pressure

Quality & Standards

Applicable clean-agent references include NFPA 2001, ISO 14520-9 and relevant approved equipment specifications. Purity, moisture, acidity and nonvolatile residue limits must be verified against the applicable purchase specification and COA.

Typical Applications

  • Data centers, server rooms and telecommunications facilities
  • Electrical control rooms and critical electronics
  • Archives, museums and high-value asset enclosures
  • Industrial machinery and enclosed process hazards, where listed

Fire Suppression Characteristics

Electrically nonconductive, clean evaporating agent that suppresses flame primarily through heat absorption with additional chemical effects. Commonly employed in total-flooding systems; suitable concentrations, discharge rates and occupied-space exposure limits are design-specific.

Engineering Considerations

Confirm system listing, cylinder pressure, agent fill density, enclosure integrity, ventilation shutdown, pressure relief and post-discharge ventilation. Thermal decomposition in fire can generate hazardous products including hydrogen fluoride.

02 / Clean Agent

HFC-236fa — Hexafluoropropane

A halocarbon clean agent particularly associated with selected portable fire extinguisher applications.

CF₃–CH₂–CF₃

Technical Specifications

CAS number690-39-1
Molecular formulaC₃H₂F₆
Molecular weight152.04 g/mol
Normal boiling point−1.4 °C
Critical temperature124.9 °C
Critical pressureApprox. 32.0 bar
Ozone depletion potential0
Physical formColorless liquefied gas under pressure

Quality & Standards

Refer to the relevant agent specification, extinguisher listing and applicable NFPA 10 or NFPA 2001 requirements, as appropriate to the equipment and application.

Typical Applications

  • Approved portable clean-agent extinguishers
  • Electrical and electronic equipment hazards
  • Selected industrial and specialized suppression equipment
  • Areas where residue-free agent discharge is desirable

Fire Suppression Characteristics

Electrically nonconductive and non-residue-forming when discharged appropriately. Fire extinguishing effectiveness depends on fuel, equipment configuration and approved design.

Engineering Considerations

Do not assume interchangeability with HFC-227ea or other agents. Verify equipment compatibility, propellant and operating conditions, occupant safety and potential hydrogen fluoride formation in flames.

03 / Clean Agent

HFC-125 — Pentafluoroethane

A high-volatility clean agent used in certain listed gaseous fire suppression systems.

CHF₂–CF₃

Technical Specifications

CAS number354-33-6
Molecular formulaC₂HF₅
Molecular weight120.02 g/mol
Normal boiling point−48.1 °C
Critical temperature66.0 °C
Critical pressureApprox. 36.2 bar
Ozone depletion potential0
Physical formColorless liquefied compressed gas

Quality & Standards

Applicable system references may include NFPA 2001 and ISO 14520 agent-specific requirements. Verify purchase specification, moisture, purity and cylinder handling requirements.

Typical Applications

  • Listed total-flooding systems for machinery and electrical rooms
  • Industrial enclosures and special hazards
  • Critical asset protection where approved by the system manufacturer

Fire Suppression Characteristics

Electrically nonconductive, fast-vaporizing agent. Design concentration, human exposure considerations and extinguishing performance depend on the hazard and approved system.

Engineering Considerations

Higher volatility than HFC-227ea influences storage, pressure management and discharge design. Use only with compatible listed equipment and account for toxic thermal decomposition products in fire.

04 / Specialized Clean Agent

HFC-23 — Trifluoromethane

An exceptionally volatile fluorocarbon used in specialized clean-agent fire suppression systems.

CHF₃

Technical Specifications

CAS number75-46-7
Molecular formulaCHF₃
Molecular weight70.01 g/mol
Normal boiling point−82.1 °C
Critical temperature26.1 °C
Critical pressureApprox. 48.3 bar
Ozone depletion potential0
Physical formColorless compressed/liquefied gas, depending on conditions

Quality & Standards

Refer to NFPA 2001, applicable ISO 14520 provisions and the approved equipment manufacturer’s agent and system specifications.

Typical Applications

  • Specialized engineered gaseous suppression installations
  • Low-temperature or demanding distribution scenarios where approved
  • Electrical and critical-equipment enclosures with compatible listed systems

Fire Suppression Characteristics

Electrically nonconductive, non-residue-forming gas with a very low normal boiling point. Its physical behavior and storage requirements differ significantly from the other HFCs listed here.

Engineering Considerations

Critical temperature is close to ordinary ambient conditions. Cylinder pressure, temperature, discharge calculations, safety provisions and handling must follow the approved system design. Thermal decomposition can generate hydrogen fluoride.

Compare

HFC Agent Comparison

PropertyHFC-227eaHFC-236faHFC-125HFC-23
CAS431-89-0690-39-1354-33-675-46-7
Molecular weight (g/mol)170.03152.04120.0270.01
Boiling point (°C)−16.4−1.4−48.1−82.1
Critical temperature (°C)101.7124.966.026.1
Ozone depletion potential0000
Typical equipmentEngineered floodingPortable / specializedEngineered floodingSpecialized engineered
Important technical and regulatory notice. HFCs have significant global warming impacts and are subject to applicable production, import, sale, use and phase-down rules, including the U.S. AIM Act and EPA regulations. Zero ozone depletion potential does not mean zero climate impact. Applications described are illustrative, not a claim of product or system approval. Only qualified professionals should design, install, charge or service suppression systems using current listings, standards, safety data sheets and applicable regulations.

Get In Touch

Request a Quote or Technical Documentation

Contact Waysmos USA about agent grade, quantity, required specification, packaging, destination, lead time, certificate of analysis and safety data sheet availability. Please identify the intended fire protection application and applicable jurisdiction.

Contact Waysmos USA

Technical references: NFPA 2001 · ISO standards catalogue · U.S. EPA HFC phasedown. Confirm current editions and applicable regulatory status before use.